Cookies helfen uns bei der Bereitstellung unserer Dienste. Durch die Nutzung unserer Dienste erklären Sie sich damit einverstanden, dass wir Cookies setzen.
Cookies help us in providing our services. By using our services, you agree that we set cookies.
OK
S7-LAN connector for Siemens S7 PLC controller - Process Informatik Entwicklungsgesellschaft mbH

S7-LAN connector for Siemens S7 PLC controller


Successor: CONNECT-Router for Din-Rail-mounting (Art.No: 9354-CONNECT-HS-ROUTER)

Network-connection for the S7-200/300/400-PLC +++ S7-adapter PPI/MPI/PROFIBUS +++ Of developer and manufacturer +++ Smallest Ethernet-gateway S7 +++ Network for each S7-PLC +++ Fast commissioning +++ Replacement for CP343-1/443-1

Industrial WIFI-Router for Unified Access
Integrated USB-port
Basic-plattform, functionality with
software-options expandable
One-click mounting

Novelty:
Variant with integrated access-protection LAN <=> bus-side as well as output of diagnostic-buffer in web-site

Networking of SIMATIC S7-PLCs (S7-200/300/400) without Ethernet-CP/CP-communicationprocessor standard-TCP/IP without changes to the hardware-configuration or PLC-program.
Compact and robust Ethernet-converter (MPI / PROFIBUS / PPI - Ethernet).
Similar to "IBH Link S7++" (IBH-Link-S7-PP, 20266), "NETLink PRO Compact", "ACCON-NetLink-PRO compact" or "NL 50-MPI".
Integration of the "old system" into the world of "new and modern systems" using S7-TCPIP with PUT/GET function.
By plugging the module onto the PPI, MPI or Profibus, this connection becomes an Ethernet port for the Industrial IoT with significant cost savings.
Thanks to the integrated multiplexer, this connection becomes a port for all supported protocols. Simultaneous and parallel communications such as WinCC, PUT/GET from S7 PLC, production-data acquisition, S7-communication-drivers and programming-packages such as Step7, TIA Portal or PG2000.

Advantages:

more...
variants:


ARTNR: 9352-ALF-UA
ALF-UA high-speed WIFI-Router for Din-Rail-mounting
Obsolete
EAN number: 4260363247221
HS-code: 85176200
Weight: 0.17 kg


ALF-Devices

ALF ALF-UA ALF-UA-TISCH
Assembly / housing Tabletop unit DIN-rail assembly Tabletop unit
Search for access. nodes Simatic-Manager/TIA --- Yes Yes
Support WPS registration Yes --- ---
Easy configuration --- Yes Yes
Restart mandatory between config changes Yes No, just switch No, just switch
Language of the web interface only GB D / GB switchable D / GB switchable
Access-Point/Client at the same time --- Yes Yes
WAN-port can be used in AP-bridge-mode --- Yes Yes
WAN-port can be used in client-bridge-mode --- Yes Yes
USB port for future expansion --- Yes Yes
Passive POE (12V) Yes --- ---

ALF-Devices

ALF ALF-UA ALF-UA-TISCH
Assembly / housing Tabletop unit DIN-rail assembly Tabletop unit
Search for access. nodes Simatic-Manager/TIA --- Yes Yes
Support WPS registration Yes --- ---
Easy configuration --- Yes Yes
Restart mandatory between config changes Yes No, just switch No, just switch
Language of the web interface only GB D / GB switchable D / GB switchable
Access-Point/Client at the same time --- Yes Yes
WAN-port can be used in AP-bridge-mode --- Yes Yes
WAN-port can be used in client-bridge-mode --- Yes Yes
USB port for future expansion --- Yes Yes
Passive POE (12V) Yes --- ---

Operating-modes of the ALF-device and their function:

Operating-mode ALF ALF-UA
AP-Router
  • Build a WiFi-network
  • LAN-port and WiFi are in the same subnet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port must be another subnet, it will be routed here
  • Build a WiFi-network
  • LAN-port and WiFi are in the same subnet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port must be another subnet, it will be routed here
AP-Bridge
  • Build a WiFi-network
  • LAN-port and WiFi are in the same subnet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port is without function
  • Build a WiFi-network
  • LAN-port, WAN-port and WiFi are in the same subnet
    ⇒ all together communicating devices must be in the same subnet
Client-Router
  • Connects to existing WiFi-network
  • LAN-port and WiFi must be in the same SubNet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port must be another subnet, it will be routed here
  • Connects to existing WiFi-network
  • LAN-port and WiFi must be in the same SubNet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port must be another subnet, it will be routed here
Client-Bridge
  • Connects to existing WiFi-network
  • LAN-port and WiFi must be in the same SubNet
    ⇒ all together communicating devices must be in the same subnet
  • The WAN-port is without function
  • Connects to existing WiFi-network
  • LAN-port, WAN-port and WiFi must be in the same SubNet
    ⇒ all together communicating devices must be in the same subnet

S7

PPI-Bus
PPI 9.6 KBit/s - 19.2 KBit/s
x
x
x
x
x
x
x
x
x
Multimaster 9.6 KBit/s - 187.5 KBit/s
x
x
x
x
x
x
x
x
MPI-Bus
19.2 KBit/s
x
x
x
x
x
x
x
x
x
187.5 KBit/s
x
x
x
x
x
x
x
x
x
1.5 MBit/s
x
x
x
x
x
x
x
x
Profibus
9.6 KBit/s
x
x
x
x
x
x
x
x
19.2 KBit/s
x
x
x
x
x
x
x
x
x
45.45 KBit/s
x
x
x
x
x
x
x
x
93.75 KBit/s
x
x
x
x
x
x
x
x
187.5 KBit/s
x
x
x
x
x
x
x
x
x
500 KBit/s
x
x
x
x
x
x
x
x
1.5 MBit/s
x
x
x
x
x
x
x
x
3.0 MBit/s
x
x
x
x
x
x
x
x
6.0 MBit/s
x
x
x
x
x
x
x
x
12.0 MBit/s
x
x
x
x
x
x
x
x
Profibus-profile
DP
x(12)
x
x
x
x
x
x
x
x
standard
x(12)
x
x
x
x
x
x
x
x
universal(DP/FMS)
x
x
x
x
x
x
x
x
RS 232
9.6 KBit/s
x(19)
x(19)
19.2 KBit/s
x
x
38.4 KBit/s
x
x
57.6 KBit/s
x(9)
x(9)
115.2 KBit/s
x(9)
x(9)
USB
USB 1.1 (6)
x(1)
x
x(2)
LAN
10/100BaseTx
x(7)
x
x
x
x
WIFI
2.4 GHz
x
TeleService operation
with S7-300/400
x(14)(18)
x(14)(18)
baud rates at TS-operation directly at the PC
9.6 KBit/s
x
x
19.2 KBit/s
x
x
38.4 KBit/s
x(8)
x(8)
57.6 KBit/s
x(8)
x(8)
baud rates at TS-operation directly with a modem
9.6 KBit/s
x
x
19.2 KBit/s
x
x
38.4 KBit/s
x
x
57.6 KBit/s
x
x
115.2 KBit/s
x
x
HMI
9.6 KBit/s
x
x
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
19.2 KBit/s
x
x
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
38.4 KBit/s
x
x
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
57.6 KBit/s
x
x
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
115.2 KBit/s
x
x
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
x(13)
update
firmware-update
x(10)
x(10)
x(15)
x(15)
x(15)
x(15)
x(15)
x(15)
x(15)
input/online help                  
keypad
x
x
x
x(21)
x(21)
x(21)
x(21)
display
x
x
x
x
x(21)
x(21)
x(21)
x(21)
PD connections (maximum)                  
PLCVCOM
1
1
1
1
1
1
1
1
RFC1006
8
8
32
32
32
AG connections (maximum)
passive subscriber
1
15
15
15
15
15
15
15
15
active subscriber
126
126
126
126
126
126
126
126
126
more functions                  
integrated PLC-firewall
x
x
x
display diagnostic-buffer in the webbrowser
x
x
x
webserver for configuration
x
x
x
x
x
Remote access over existing VPN-channel
x
x
x
x
x
Access via existing WLAN-channel
x
x
x
x
x
status/control variable
x
x
x
x
x
S7 on S7/S5 DB exchange
x
x
x
x
x
S5 on MPI DB exchange
only as S5toMPI
S7 on MPI (Send/Fetch)
x
x
x
x
x
Profinet Gateway
x
x
x
x
x
Time in PLC from NTP-server
x
x
x
x
x
galvanic separation                  
to the bus (screen connected through)
1KV
1KV
1KV
1,5KV
1KV
1,5KV
1,5KV
1,5KV
1,5KV
mounting                  
wall monuting
(with opt. wall mounting-set)
x
x
x
x
upgrading with
CheapConn+cable
x
x
x
x
supports
WIN 98
x
x(3)
x
x
x
x
x
WIN 98 SE
x
x
x
x
x
x
x
x
x
WIN ME
x
x
x
x
x
x
x
x
x
WIN NT
x
x(5)
x(5)
x
x(5)
WIN 2000
x
x
x
x
x
x
x
x
x
WIN XP Home (4)
x
x
x
x
x
x
x
x
x
WIN XP Professional
x
x
x
x
x
x
x
x
x
Vista(32bit)
x
x
x
x
x
x
x
x
x
Win7(32bit)
x
x
x
x
x
x
x
x
x
Win7(64bit)
(22)
x(23)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
Win8/8.1
(22)
x(23)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
Win10
(22)
x(23)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
Win11
(22)
x(23)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)
x(20)

(1) just with USB-cable plug <-> plug, type A <-> A, item number: 9352.1
(2) just with USB-cable plug <-> plug, type A <-> mini B, item number: 9352.3
(3) only serial communication
(4) Siemens Step7 V5.2 and higher dont run with this operationing system
(5) USB-communication is only possible with the special driver for Win NT
(6) USB 2.0 is backward compatible to 1.1
(7) Cable is designed for direct connection to PC network card socket. It can also be a hub / switch
with uplink port or operated at a hub / switch with automatic detection of assignement and adaptation
(8) only in combination with the MPI-Speed-driver („continously-active“)
(9) Siemens Step7 supports these baud rates only with the MPI-Speed-Utility
(10) Update directly with PC or via Tele-Network if the cable is connected to a device of the
Tele-Network-family (Tele-Link, Tele-Book or Tele-Professional)
(11) only in the mode: MultiMaster-Mode
(12) up to a maximum baud rate of 187.5 KBit/s
(13) In this transmission, the baud rate is irrelevant, because it communicates via a virtual COM-port.
(14) with the use of the TS-adapter / item number: 9350.TS
(15) Update directly with PC and TIC-driver
(18) Operation requires Step 7 with additional software Tele-Service (TS) from Siemens
(19) only at PPI-communication possible
(20) Only with TIC-driver
(21) with integrated webserver possible
(22) No support of Siemens Step7-software possible
(23) Only with USB and with TIC-driver

S5

device type
S5-90U
x
+ext. 24V
+ext. 24V
x
x
x
S5-95U
x
+ext. 24V
+ext. 24V
x
x
x
S5-100U
x
+ext. 24V(3)
+ext. 24V
x
x
x
S5-115U
at 944 + 9359-8
at 944 + 9359-8 + ext. 24V (4)
x
x
x
x
S5-135U
at 928B + 9359-8
at 928B + 9359-8 +ext. 24V (6)
x
x
x
x
S5-155U
x
x
x
x
x
x
S5-AG110S
+9359-5-150 + 9359-4
+ ext. 24V (3)
+9359-5-150 + ext. 24V
S5-AG130W/B
+9359-5-150 + 9359-4
+ ext. 24V (3)
+9359-5-150 + ext. 24V
S5-AG150A/K/S/U
+9359-5-150 + 9359-4
+ ext. 24V (3)
+9359-5-150 + ext. 24V
CP-143
x
x
x
CP-521
+CP521 adapter
       
+CP521 adapter(1)
CP-523
+CP523 adapter
       
+CP523 adapter(1)
CP-525      
+9359-5(1)
CP-526
x
   
x
 
x
CP-527
x
   
x
 
x
CP-528
x
   
x
 
x
CP-544
x (7)
   
x (7)
 
x (7)
CP-5430
x
   
x
 
x
CP-5431
x
   
 
IP-246
x
   
x
 
x
IP-247
x
   
x
 
x
IP-252
x
   
x
 
x
IP-266
 
x
+9359-4(1)
WF-470
SIN-805
+9359-6 + ext. 24V(5)
+9359-6 + ext. 24V(8)
+9359-6(1)
SIN-820
+9359-6 + ext. 24V(5)
+9359-6 + ext. 24V(8)
+9359-6(1)
SIN-840
+9359-6 + ext. 24V(5)
+9359-6 + ext. 24V(8)
+9359-6(1)
SIN-850
+9359-6 + ext. 24V(5)
+9359-6 + ext. 24V(8)
+9359-6(1)
SIN-880
+9359-6 + ext. 24V(5)
+9359-6 + ext. 24V(8)
 
+9359-6(1)
Connection on PC
RS232-port
Ethernet RJ45
Ethernet RJ45 / WLAN/WIFI
USB-port type A
RS232-port
RS232-port
max. prolongation: 300m (UNI-extension) 300m (S5-LAN-extension) +ext. 24V 100m (PG-USB-extension)   300m (UNI-extension)

(1) ISO adapter can not be used because the required supply voltage on the PG interface of the module is not present.
(2) At the CPU 6ES5 102-8MA02 Release 3 is a PG-ISO-Adapter or Netz-Adapter additional required.
(3) With S5-LAN++ from HW V2.3 [2010] the "Netz-Adapter" is no more needed, this version has included current-sources.
(4) With S5-LAN++ from HW V2.3 [2010] no accessories are needed, this version has included current-sources.
(5) With S5-LAN++ from HW V2.3 [2010] the Sinum-Adapter 9359-6-USB is needed.
(6) Only for CPU928B with PG-ISO-Adapter and ext. 24V DC, unless there is an S5-LAN++ from HW V2.3 [2010] used.
(7) CP544 has bolts at the programming-interface. The products do not fit 100% on this interface.
(8) With S5-BRIDGE the Sinum-Adapter 9359-6-USB is needed.

Remote maintenance

TELE LINK NETWORK
         
 
secured modem-protocol
additional software needed
Siemens TS -Software
Siemens TS -Software
VPN-Client
VPN-Client
Providing WinTELEPROF-software
modem
analogue/ISDN
analogue
opt. via PCMCIA
analogue/GSM
analogue/ISDN/GSM
internet-connection
internet-connection
internet-connection
modem for world wide use
interfaces
MPI/Profibus
9600-12MBd
9600-12MBd
9600-12MBd
9600-12MBd
RS232
2x
2x
2x
1x
1x
TTY
2x
2x
2x
1x
PCMCIA
2x (optionally)
1x
1x
Ethernet
10/100BaseTx
1x
1x
5x
USB
2x
1x
LCD-display
instead 10 LEDs
instead status-LED
instead webserver
instead webserver
supported PLC-protocols *
S7
S5
✓ (optional)
✓ (optional)
Pilz PSS
✓ (optional)
✓ (optional)
Allen-Bradley
✓ (optional)
✓ (optional)
AEG
✓ (optional)
✓ (optional)
Bosch
✓ (optional)
✓ (optional)
Telemecanique
✓ (optional)
✓ (optional)
GE-Fanuc
✓ (optional)
✓ (optional)
Klöckner-Moeller
✓ (optional)
✓ (optional)
Mitsubishi
✓ (optional)
✓ (optional)
SMS-sending/Pager(S5/S7)
✓ (no pager)
only for analogue / ISDN
HMI-messaging module(S5/S7)
SMS-receive with GSM
DTMF with analogue
e-mail-dispatch
FAX-dispatch(S5/S7)
✓ (optional)
✓ (optional)
only for analogue / ISDN
PLC-data coupling(S5/S7)
✓ (optional)
✓ (optional)
ASCII-transfer from S5/S7
✓ (optional)
✓ (optional)
only with ASCII-LAN
internet-coupling
Usage as dial-up-router
power supply
24V/DC
24V/DC
24V/DC
24V/DC
24V/DC
24V/DC
24V/DC
24V/DC
dimensions w x h x d (in mm)
High: 67 x 280 x 170
FLAT: 300 x 175 x 70
300 x 175 x 66
235 x 162 x 37
90 x 162 x 54
40 x 125 x 115
42 x 15 x 65
65 x 43 x 17
154 x 92 x 28

* other PLC types on request

Wöhrle Belgium B.V.B.A.
Mechelen , Belgium
www.wohrle.be
Novelty:
Variant with integrated access-protection LAN <=> bus-side as well as output of diagnostic-buffer in web-site

Networking of SIMATIC S7-PLCs (S7-200/300/400) without Ethernet-CP/CP-communicationprocessor standard-TCP/IP without changes to the hardware-configuration or PLC-program.
Compact and robust Ethernet-converter (MPI / PROFIBUS / PPI - Ethernet).
Similar to "IBH Link S7++" (IBH-Link-S7-PP, 20266), "NETLink PRO Compact", "ACCON-NetLink-PRO compact" or "NL 50-MPI".
Integration of the "old system" into the world of "new and modern systems" using S7-TCPIP with PUT/GET function.
By plugging the module onto the PPI, MPI or Profibus, this connection becomes an Ethernet port for the Industrial IoT with significant cost savings.
Thanks to the integrated multiplexer, this connection becomes a port for all supported protocols. Simultaneous and parallel communications such as WinCC, PUT/GET from S7 PLC, production-data acquisition, S7-communication-drivers and programming-packages such as Step7, TIA Portal or PG2000.

Advantages:
  • Simple and fast networking
  • Multiplexer for all protocols
  • Integration as S7 controller with CP 343-1
  • Access to S7 data via S7-TCP/IP with PUT/GET
  • Module search without "annoying" network-card-selection
  • Free virtual-com-port for non-Step7-applications
  • Qualified support
  • Comprehensive documentation
  • No SimaticNet required for operation/configuration
  • STEP7 64-bit support
  • Integration into the TIA-Portal
  • Supports DHCP

Connectivity:
  • S7-LAN module directly connected to the PC/device with a patch cable
  • S7-LAN module directly connected to the PC/device with a crosslink cable
  • S7-LAN connected to the PC/device via a switch or hub

Features:
  • every SIMATIC-S7 (S7-200/300/400) into Network
  • SIMATIC S7-protocols (S7Comm and ISO-on-TCP (RFC 1006))
  • Ethernet-RJ45 socket with 10/100 MBit/s with autonegotiation
  • Commissioning is very simple: plug it into the PPI, MPI-bus or PROFIBUS of the SIMATIC S7 controller and start working
  • Integrated multiplexer (visualization, programming, remote maintenance and simultaneous use of all protocols without special configuration), also via standard router
  • Parallel use of the channels (simultaneously 8 x channels for programming, visualization and remote maintenance can be used directly/routed)
  • Supported controllers (S7-200, S7-300, S7-400, FM modules, Sinamix, Sinumerik, MicroMaster and other drives/converters (such as SEW-EURODRIVE converters)
  • Supported data areas (inputs, outputs, markers, data blocks, timers and counters)
  • Supported scenarios (programming adapter for S7 programming packages, access to the S7 data via S7-TCP/IP with PUT/GET and routing of SIMATIC S7 controllers as well as time server for time and also bus diagnostics)
  • Supported platforms (S7-TCPIP RFC1006 communication platform-independent, communication driver/configuration tool TIC for Windows XP, Win7/8/10/11)
  • Replacement for CP343-1/443-1 or IE/PB-Link, connected directly to MPI or Profibus (inexpensive)
  • with Profibus for S7-300 faster than CP343-1
  • PG/PC-adapter for Simatic-Manager Step7 and TIA-portal
  • fastest installation into Network (less than 3 minutes)
  • automatic detection of baudrate
  • automatic usement of cyclic bus-parameter-protocols
  • no bus-knowledge required / automatic-protocol and baud-rate detection
  • download TIC-driver for STEP-7/TIA-Portal
  • Programming and visualization at the same time (8 S7-connections (direct / routed) at the same time)
  • compatible to S7-TCP/IP RFC1006, WinCC (flex), OPC UA with Universal communication Industry 4.0, the IP-S7LINK SDK as well as all common OPC-servers
  • no HW-Config change necessary
  • no change of PLC-software necessary
  • including Classic OPC-DA-Server-lite (max. 100 variables)
  • with PG-diagnostic-port (occupied slot with 9pin PG-port free again)
  • DPV1-master of class 2 and supports all functions that a PG supports:
    • Diagnosis, configuration and programming of controllers (via software such as Simatic-Manager, TIA-Portal)
    • Diagnosis and configuration of DP-slaves (via software such as Starter)
  • active module, no influencing other bus users in the system
  • active PUT/GET (in module integrated) replaces expensive CP´s for PLC-couplings
  • Supply from S7-PLC or 24V DC external
  • CE/EMC compliant design
  • Scope of delivery (TIC driver, module itself and quick start guide)
  • Search for modules across all Network-cards (no Network-card-selection as with other providers)
  • Variable status in web interface
  • RFC1006 connection status
  • PLC-time via PG-protocol
  • TCPIP-device writes/reads DB in S7-PLC
  • Bus-diagnostics (output of error-counters, spikes)
  • RFC1006 for S7-200 (1. Generation)
  • virtual COM-port-driver for other serial S7-applications
  • Standard HMI-applications can read/write data via RFC1006 and the module


Applications:

  • Operational data collection, SCADA of non-networkable controllers
  • KTP-panel to S7-PLC with MPI-/Profibus-interface
  • PUT/GET from S7-1500/1200/300/400 (PN-CPU or with ethernet-CP) with specified and unspecified connection
  • VPN(Virtual Private Network)-remote-maintenance, maintenance of the PLC via the Internet
  • cyclic time reading from NTP-server and setting in the connected PLC
  • coupling with DB-transfer to S7-LAN, S7-Gateway, S7-CP, S5-LAN++ or also S5-Gateway
  • any TCP-device writes/reads DBs in the S7-300/400 controller
  • monitor variables in the WebServer without a Step7 programming-package
  • analysis option of the connected bus-system with spikes- and errors-counter
  • Parameterization of field devices and drives (DPV1)
  • With IP-S7-Link-DLL high-level languages-access
  • PLC-PLC-communication (regardless of subnet boundaries, prolongation MPI/DP-bus over network)

TIC-(Totally Integrated Communication)-driver for Step7/TIA-Portal for Win XP/VISTA/7/8/10/11 32/64 Bit:
TIC firmware / configuration-tool / Step7-/TIA-driver

Product overview:

S7-LAN is a reliable and handy S7-network-adapter for PPI-,MPI- and PROFIBUS. Designed for 24/7-operation. The compact design in the PROFIBUS-connector-case and the power supply directly from the MPI/DP-port of the CPU allow to be connected a PLC to the network in less than 3 minutes.
bus protocols/bus profile, incl. baudrate and HSA are recognized independently and automatically and configured.
HMI-devices, for e.g. actual panel-series, as well as any other S7-Ethernet device, direct connect per S7-TCP-IP.
With TIC-driver (configurations-tool and driver) from download-area without changes on the project of Siemens TIA, Simatic Step7 Manager and WinCC-projects communication.
Another advantage is the easy handling of the S7-LAN. The convenient configuration is carried out directly in STEP7 or the PG/PC-interface-dialog. The detection of whether the S7-LAN is connected to a 10 MBit or 100 MBit network takes place automatically. Power is supplied directly from the MPI / DP interface. The connection to passive participants or VIPA-PLC is possible via the integrated 24V-plug.
The S7-LAN is connected to the bus-socket of the PLC and via the hub or directly to the PC. Then install the TIC-driver on the PC. Assign the IP-address with the TIC-configuration-program and go ONLINE. The installation process is completed so quickly.

Configuration:

S7-LAN is designed for quick commissioning. After the module has been plugged into the bus or externally supplied with 24V DC, only an IP address is assigned via the TIC-driver or directly via the Web-interface . The controllers can then be accessed from the network.
With the TIC-driver, there is no need for any additional installation outside of the Siemens world. The configuration takes place directly in the PG-PC interface settings and is therefore optimally integrated. Any network device that speaks S7-TCP/IP RFC1006, such as HMI-devices or PGs, can access the module directly.
In the S7-project itself, the adapter can be integrated using a placeholder entry. This is not a must, operation without project change is possible immediately. The S7-communication runs directly via S7-TCP/IP and expands each MPI-/PROFIBUS with a network gateway. It doesn't matter which control types (S7-200 / S7-300 / S7-400) are connected to the fieldbus of the PLC network.
Profinet WLAN panel connection
Produkbild

Simply connect your panel to your Profibus via WLAN.
Mobile workplaces are optimally connected.
You will be able to link additional applications such as PDs, visualizations or ERP systems at the same time.

Current S7 panels via WLAN to the S5 controller
Produkbild

Connect each S7-TCP-IP panel to your S5.
Now also available via WLAN for mobile workstations.
PARALLEL several panels and even simultaneous PG connections possible.
Include hard-to-reach places in your ERP system.

Link S7-TCP-IP Panel to MPI Profibus over WiFi
Produkbild

Use the latest S7-TCP-IP panels for your MPI / Profibus.
Thanks to WLAN also usable for mobile platforms or cranes.
Connect several nodes at the same time via a network module.
Simultaneous access from different systems possible.

Link S7-TCP-IP Panel to MPI Profibus over WiFi
Produkbild

Use the latest S7-TCP-IP panels for your MPI / Profibus.
Thanks to WLAN also usable for mobile platforms or cranes.
Connect several nodes at the same time via a network module.
Simultaneous access from different systems possible.

Wireless around the Allen-Bradley-PLC
Produkbild

Move wirelessly around the Allen-Bradley-PLC and communicate for example ONLINE in the status

Wireless around the Beckhoff-PLC
Produkbild

Move wirelessly around the Beckhoff-PLC and communicate for example ONLINE in the status

Wireless around the Bosch-PLC
Produkbild

Move wirelessly around the Bosch-PLC and communicate for example ONLINE in the status

Wireless around the Eaton-PLC
Produkbild

Move wirelessly around the Eaton-PLC and communicate for example ONLINE in the status

Wireless around the machine with LAN-port
Produkbild

Move wirelessly around the machine with LAN-port and communicate for example ONLINE in the status

Wireless around the Mitsubishi-PLC
Produkbild

Move wirelessly around the Mitsubishi-PLC and communicate for example ONLINE in the status

Wireless around the Moeller-PLC
Produkbild

Move wirelessly around the Moeller-PLC and communicate for example ONLINE in the status

Wireless around the Pilz-PLC
Produkbild

Move wirelessly around the Pilz-PLC and communicate for example ONLINE in the status

Wireless around the ProfiNet-PLC
Produkbild

Move wirelessly around the ProfiNet-PLC and communicate for example ONLINE in the status

Wireless around the S5-PLC
Produkbild

Move wirelessly around the S5-PLC and communicate for example ONLINE in the status

Wireless around the S7-PLC
Produkbild

Move wirelessly around the S7-PLC and communicate for example ONLINE in the status

Wireless around the Schneider-PLC
Produkbild

Move wirelessly around the Schneider-PLC and communicate for example ONLINE in the status

Supply voltage: 24V DC +/- 20%
Power consumption: 1,2 watt
Display: status-LEDs
Handling/Configuration: with integrated webserver
Interfaces:
to antenna:
RP-SMA-female connector (reverse polarity) with 5 dBi
(Power out: 20 dB)
to the PLC:
10/100BaseTX RJ45-ethernetplug
to the PD/PC:
WLAN connection (802.11 b/g/n)
Security WEP 64/128bit
WPA (TKIP with IEEE 802.1x)
WPA2 (AES with IEEE 802.1x)
WPA Mixed
Operating temperature: 0 - 55°C
Case: plastic clamping-case
Dimensions: 114 x 100 x 22.3 mm
 
Scope of delivery: ALF-UA
WIFI-stub-antenna
All prices plus costs of delivery, shipping insurance and VAT.

accessories:

9391.1
24V DC power-supply unit 625mA

Primary 110V - 240 VAC Euro+USA-plug
Quickbestellung INFOMAIL
by e-mail
59,00 €
plus VAT. and shipping


9379-AV
Antenna extension GSM/LTE/WIFI
Base-price + cable length #9379-AV-L
Quickbestellung INFOMAIL
by e-mail
40,00 €
plus VAT. and shipping


9379-AV-L
Additional charge for special length
for antenna extension per meter 4,- Euro
Quickbestellung INFOMAIL
by e-mail
4,00 €
plus VAT. and shipping


9352-ALF-ANT-WAND
Stationary antenna for wall fastening

for ALF and CONNECT-ROUTER, cable length: 2,5m for indoor and outdoor use incl. wall holder
Quickbestellung INFOMAIL
by e-mail
85,00 €
plus VAT. and shipping


9391-USB
USB-powercable for 24V DC, max. 3W

USB-plug type A to 2 open braids 24V DC, maximum current: 125mA (for PC 100mA) length: 5m
Quickbestellung INFOMAIL
by e-mail
95,00 €
plus VAT. and shipping


price on request
plus VAT. and shipping

9352-ALF-SEKT-ANT
Sector antenna for ALF

Sector antenna with 17dBi power gain and bundled radiation. Connection cable optional
INFOMAIL
by e-mail
price on request
plus VAT. and shipping

9352-ALF-RICHT-ANT
Beam antenna for ALF

Beam antenna with 17dBi power gain for classic radio link connection cable optional
INFOMAIL
by e-mail
price on request
plus VAT. and shipping

9350-9-CHP-24V-OUT
CheapConn Busconnector with 24V-output

Comfortable power supply for ALF, TONI, WLAN-Klemme and CONNECT-ROUTER
Quickbestellung INFOMAIL
by e-mail
85,00 €
plus VAT. and shipping


9636-TCPIP.1M
Patch-cable 1m, Cat5e, shielded
RJ45 plug <=> RJ45 plug, 1:1
Quickbestellung INFOMAIL
by e-mail
15,00 €
plus VAT. and shipping


9352-ALF-ANT
Magnetic base antenna for indoor use

for ALF, ALF-UA- S5-/S7-BRIDGE, CONNECT CONNECT-ROUTER cable length: 1,5m
Quickbestellung INFOMAIL
by e-mail
83,00 €
plus VAT. and shipping


9636-CROSS
Cross-cable 3m Cat5+, shielded

RJ45 plug <=> RJ45 plug, twisted pinning
9636-TCPIP
Patch-cable 3m, Cat5+, shielded

RJ45 plug <=> RJ45 plug, 1:1
All prices plus costs of delivery, shipping insurance and VAT.

9352-ALF-UA
ALF-UA high-speed WIFI-Router for Din-Rail-mounting Obsolete

Successor: CONNECT-Router for Din-Rail-mounting (Art.No: 9354-CONNECT-HS-ROUTER)
Industrial WIFI-Router for Unified Access Integrated USB-port Basic-plattform, functionality with software-options expandable One-click mounting
Quickbestellung INFOMAIL
by e-mail
0,00 €
plus VAT. and shipping



maximum 3 articles
9352-ALF-UA-TISCH
ALF-UA high-speed WIFI-Router table-device Obsolete

Successor: CONNECT-Router table-device (Art.No: 9354-CONNECT-ROUTER)
Industrial WIFI-Router for Unified Access Integrated USB-port Basic-plattform, functionality with software-options expandable table-device
Quickbestellung INFOMAIL
by e-mail
0,00 €
plus VAT. and shipping



maximum 3 articles
0,00 €
plus VAT. and shipping



maximum 3 articles

All prices plus costs of delivery, shipping insurance and VAT.

9352-ALF-ANT
Magnetic base antenna for indoor use

for ALF, ALF-UA- S5-/S7-BRIDGE, CONNECT CONNECT-ROUTER cable length: 1,5m
Quickbestellung INFOMAIL
by e-mail
83,00 €
plus VAT. and shipping


9359-LAN
S5-LAN++

Industrial Ethernet <> S5 PD-interface (TTY) Including Gateway Plus and S7-TCP / IP functions
Quickbestellung INFOMAIL
by e-mail
452,00 €
plus VAT. and shipping


9352-LANCON
S7-LAN connector for Siemens S7 PLC controller

Network-connection for the S7-200/300/400-PLC +++ S7-adapter PPI/MPI/PROFIBUS +++ Of developer and manufacturer +++ Smallest Ethernet-gateway S7 +++ Network for each S7-PLC +++ Fast commissioning +++ Replacement for CP343-1/443-1
Quickbestellung INFOMAIL
by e-mail
423,00 €
plus VAT. and shipping


9391.1
24V DC power-supply unit 625mA

Primary 110V - 240 VAC Euro+USA-plug
Quickbestellung INFOMAIL
by e-mail
59,00 €
plus VAT. and shipping


Automatic-mode

Main downloads

Versionstory

Other downloads

Extension

Support-videos